Description:
The Liger series convert DC power into AC power. With a continues output and compact design , the unit is ideal for running Tvs, stereos, laptop and desktop computers and other home appliances. Liger series will automatically transfer to UPS and provide power when AC supply is interrupted unexpectedly.
Feature:
- Auto restart while AC current resumes
- Rapid intelligent charger 10 A to 20 A selectable
- Reverse Battery Safety Protection.
- Provides Deep Discharge, Over Charge, Short Circuit, Overload Battery Short, Over Voltage, Under Voltage & Reverse Battery Safety Protection etc.
- Multi-function LCD with LED indication and buzzer alarms
- High efficient DC-to-AC Conversion, minimizing energy loss
- Recommended MF Battery (Flooded lead acid battery can also be used)
- Intelligent 2-stage charger control for efficient charging and preventing overcharge
Specification:
Capacity: 1000W / 1500VA
AC Input
- Nominal Voltage: 220/230/240VAC
- Input Voltage Range: 90~280VAC
- Nominal Frequency: 50/60Hz (Auto Detection)
Technology: Inverter
Input Voltage Range Sector
- Narrow: 170-280VAC
- Wide: 90-280VAC
- Voltage: 230VAC + 10-/18%
Inerter Mode Output
- Frequency: 50/60Hz+-0.5Hz
- Efficiency (AC to Dc): >95%
- Waveform: Modified Sine Wave
- Efficiency (AC to Dc): >95%
- Efficiency (DC to Ac): >80%
Battery:
Charger
- Charging Voltage (Vbat<12.5V): 14.4+/-0.4V
- Charging Voltage (Vbat<12.5V): 13.7+/-0.2V
- Charger: Charging Current: 10A+-2A
- Charger: Charging Current: 20A+-2A
- Overcharging Protection: 16V+/-0.4V
Transfer
- Transfer Time : Typical 15-20ms, 40ms max
- Line Mode: Green LED blinks or right steadily
Indicator
- Battery Mode: Yellow LED lights
- Overload / fault: Red LED blinks or lights steadily
- Low Battery Voltage in Battery Mode: Beeps every 2 seconds
Audible Alarm
- Overload: Beeps every 0.5 seconds
- Fault: Beep continuously
Environment
- Temperature: 0~40`C
- Dimension (mm) DxWxH: 255x80x224
- Net Weight: 2.5KG